Quality System Certification |
S09001:2015
|
Application |
Power factor correction or power system filtering for indoor low-voltage power systems
|
Applicable Height |
Altitude below 2,000 meters (other heights can be customized)
|
Frequency |
60Hz/50Hz
|
Capacity Inaccuracy |
-5%~+5%
|
Ambient Temperature |
-25°C~50℃ (24-hour average temperature less than 40℃, annual average temperature less than 30℃. Other temperature types can be customized)
|
Maximum Permissible Voltage |
-1.1 times the rated voltage (within 8 hours in 24 hours)
-1.15 times the rated voltage (within 3 hours over a 24-hour period)
-1.2 times the rated voltage (5 minutes, up to 200 times)
-1.3 times the rated voltage (1 minute, up to 200 times)
|
Maximum Permissible Current |
Rated current 1.3 times
|
Dielectric Loss |
Less than 0.02% or 0.2w/kvar
|
Capacitor Loss |
Less than 0.1% or 1W/kvar
|
Interphase Withstand Voltage Test |
2.15 times the rated voltage, applied voltage for 10 seconds
|
Phase-to-ground Withstand Voltage Test |
3000VAC, applied for 10 seconds
|
Discharge Characteristic |
After the capacitor has been disconnected from the power supply for 2 to 3 minutes, the residual voltage will automatically drop below 75V.
|
Security |
Built-in overpressure protection device with overload and fault protection
|
Allow Surge |
200 times the rated current
|
Dielectric |
Polypropylene plastic film (PP)
|